RQRM6-12-24 series SF6 Gas-insulated metal-enclosed switchgear (GlS) is a new-model medium voltage ring switchgear developed by ROOQ Electric Group. The GIS is applicable to distribution devices of three-phase 50HZ and rated voltage of 12KV. It is widely used in industrial and civil cable ring nets and power supply terminals, especially applicable to the power systems of small size secondary distribution stations, on-off rooms, industrial and mining enterprises, urban communities, airports, rail way, tunnels, multi-storey buildings for power distribution.
Environmental conditions for Normal Use
1. Ambient temperatur: +40°C (maximum)to-40°C (minimum);
2. Ambient relative humidity: the average daily not more than95%, not more than 90% monthly;
3. Above sea I eve I:not more than 2000m;
4. Earthquake intensity:not to exceed magnitude 8;
5. The pIaces shall be without fire, the risk of explosion, chemical corrosion and fierce vibration.
Rated voltage | KV | 12/24 |
Rated frequency | HZ | 50 |
Rated current for ring loop | A | 630 |
Rated current of fuse loop (Max.) | 125 | |
Rated active breaking current/breaking times | A/Times | 630/20 |
Rated breaking current for cable charge/breaking tines | A/Times | 40/20 |
Rated short-time withstand current | KA | 20 |
Rated peak withstand current | KA | 50 |
Rated short circuit duration | S | 3 |
Rated short-circuit making current | KA | 50 |
Rated transfer current | A | 1750/1400 |
1min power-frequency withstand voltage: | KV | 63/79 |
Lightning impact withstand voltage: | KV | 125/145 |
Rated SF6 gas pressure (pressure from the meter at 20°C) | MPa | 0.04/0.02 |
Mechanical endurance (Load Switch/Earth Switches) | Times | 5000/2000 |
Annua I leakage rate of SF6 gas | <0.025% | |
Protection Level | Gas compartment | IP67 |
Enclosure | IP3X |