GGD LOW VOLTAGE DISTRIBUTION PANEL

GGD AC low voltage distribution cabinet is used for power and lighting in distribution system. And the power conversion, distribution and control of distribution equipment. Applicable to power plants, power stations, industrial and mining enterprises, etc


Executive standard

IEC 60439-1 Low voltage switchgear and control-gear assemblies

Part 1:Type test and partial type test assemblies

GB 7251.1 Low voltage switchgear and controlgear assemblies

Part 1: type test and partial type test assemblies

JB/T 9661-1999 Low voltage withdrawable switchgear and other standards


Service Environment

1. For indoor use, the altitude shall not exceed 1000m;

2. The ambient air temperature is - 5 ℃ ~ + 40 ℃, and the average temperature within 24 hours shall not exceed + 35 ℃. If it exceeds, the capacity shall be reduced according to the actual situation;

3. the relative humidity shall not exceed 50% at the maximum temperature of + 40 ℃, and a large relative humidity is allowed at a lower temperature. For example, 90% at + 20 ℃. It shall be considered that the influence of condensation may occur occasionally due to the change of temperature. The daily average value shall be less than 95%, and the monthly average value shall be less than 90%;

4. The daily average value of steam shall not be greater than 2.2 * 10-3mpa, and the monthly average value shall not be greater than 1.8 * 10-3mpa;

5. The inclination between the equipment and the vertical plane shall not exceed 5 degrees during equipment installation.

6. The seismic intensity shall not exceed 8 degrees

7. No frequent violent vibration

8. The surrounding air shall not be polluted by corrosive or combustible gases, water vapor, etc

9. In case of special use environment or other requirements, it is necessary to negotiate with the manufacturer


Technical Data

Item

Rated Voltage
(V)

Rated current
(A)

Rated short-circuit breaking current(KA)

Rated short-time withstand current(KA)

Rated peak withstand current(KA)

GGD1

380

A

1000

15

15

30

B

600(630)

C

400

GGD2

380

A

1500(1600)

30

30

63

B

1000

C

800

GGD3

380

A

3150

50

50

105

B

2500

C

2000


Cabinet structure

1. The frame is locally welded and assembled with 8MF cold-formed steel. Its rigidity and bearing capacity meet the installation requirements of electrical components. The frame is provided with installation holes arranged according to e = 20mm and E = 100mm modules respectively, so as to improve the universality of product assembly.

2. The main bus is arranged behind the upper part of the cabinet, and the ZMJ bus clamp is a building block composite structure. Hot injection molding with high flame retardant PPO alloy material has high mechanical strength and insulation, can withstand 50kA effective value and 105kA peak dynamic and thermal stability impact force, and the long-term allowable temperature can reach 120 ℃.

3. The overall dimensions of the frame are shown in the table below:

Item

H (mm)

W(mm)

D(mm)

GGD1;GGD2

2200

600、800、1000

600

GGD3

2200

800、1000、1200

600、800


4. 1000mm and 1200mm wide cabinets adopt asymmetric (800 + 200), (800 + 400) double door structure on the front, whole door structure on the 600 and 800 wide cabinets, and symmetrical double door structure on the back of the cabinet. It not only solves the protection of direct electric shock, but also improves the overall beauty and strength, and is also convenient for the manufacturer to form standardized production.

5. The cabinet door is connected with the frame by galvanized rotating shaft hinge. Easy installation and disassembly. Rubber fillets are added at the edge of the door. When the door is closed, the fillets between the door and the cabinet have a certain compression stroke to prevent direct collision between the door edge and the cabinet, and improve the protection grade of the door.

6. The protection level of the front, back, top and both ends of the cabinet shall reach IP30, and can also be selected between IP20 and IP40 according to the requirements of users.



Hot Products

Low Voltage Distribution Panel

Low Voltage Distribution Panel

33KV Transformer

33KV Transformer

3 Phase Auto Transformer

3 Phase Auto Transformer

Single Phase Oil Transformer

Single Phase Oil Transformer

SF6 Ring Main Unit

SF6 Ring Main Unit

Amorphous Alloy Transformer

Amorphous Alloy Transformer

Withdrawable Switchgear

Withdrawable Switchgear

Padmount Substation

Padmount Substation

Single Phase Isolation Transformer

Single Phase Isolation Transformer

Single Phase Pad Mounted Transformer

Single Phase Pad Mounted Transformer

Pad Mounted Distribution Transformer

Pad Mounted Distribution Transformer

KYN61 40.5 Switchgear

KYN61 40.5 Switchgear

Outdoor Vacuum Circuit Breaker

Outdoor Vacuum Circuit Breaker

Vauum Load Switch

Vauum Load Switch

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours